Compressor over temperature condition
In priority order: • Let the EACS cool down for 60 minutes. Read compressor temperature sensor input value using the UDS service. • Check the cooling system • Check visually wiring harness • Check wiring harness connection • Check Thermal switch • Check the environment condition • Check the lack of oil in the compressor • Check the oil sensor switch Details regarding how to, please check the service manual §Trouble shooting.
What you'll see
Low system pressure Possibly compressor very hot
System reaction
EACS not running Red stop lamp lit
Diagnostic depth
The DTC is set to active if: • The compressor temperature sensor indicate a temperature too high condition The DTC is set to inactive if: • The compressor temperature sensor indicate a temperature OK condition for at least 30 seconds The limits for the compressor temperature sensor input are as follows: • < 1 kohm: Temperature OK • > 10 kohm: Temperature too high
One or more of the following: • Insufficient coolant flow • Coolant temperature too high • Sensor cable harness defective or disconnected • Coalescence filter is defective • Heat exchanger clogged • Ambient temperature too high • Oil level in compressor housing too low • Compressor defective