S Scania Multi 📌 unpin — ▢ ×
Pin a chassis:
Home Vehicle Parts Information Workshop Diagnostics Search Back Forward Help
V
DTC › EACS3 EACS3 / 010801

Compressor over temperature condition

â–¶ How to fix

In priority order: • Let the EACS cool down for 60 minutes. Read compressor temperature sensor input value using the UDS service. • Check the cooling system • Check visually wiring harness • Check wiring harness connection • Check Thermal switch • Check the environment condition • Check the lack of oil in the compressor • Check the oil sensor switch Details regarding how to, please check the service manual §Trouble shooting.

What you'll see

Low system pressure Possibly compressor very hot

System reaction

EACS not running Red stop lamp lit

Diagnostic depth

Detection

The DTC is set to active if: • The compressor temperature sensor indicate a temperature above CompTempHighLimit(1) for 500 ms The DTC is set to inactive if: • The compressor temperature sensor indicate a temperature below CompTempOkLimit(2) for 500 ms AND • At least 30 seconds have elapsed since the DTC was set to active (1) CompTempHighLimit is an EOL parameter, default value 125 °C. (2) CompTempOkLimit is an EOL parameter, default value 100 °C.

Possible cause

One or more of the following: • Insufficient coolant flow • Coolant temperature too high • Sensor cable harness defective or disconnected • Coalescence filter is defective • Heat exchanger clogged • Ambient temperature too high • Oil level in compressor housing too low • Compressor defective

{ } Raw XML
diag